Southern California Edison

Southern California Edison (SCE, https://www.sce.com) is a large electric utility with over 15 million customers and covers 50,000 square miles in southern California. SCE has been a valuable partner and customer of Cleaveland Price (C/P) since before the year 2000. California has suffered from over 4,400 wildland fires and 140,000 acres burned on average per year over the last five years (https://www.fire.ca.gov/our-impact/statistics). It was clear that SCE needed methods to mitigate the wildfire risk.

SCE began a project to investigate worldwide best practices for wildfire mitigation and identified the approach taken in Australia, known as Rapid Earth Fault Current Limiting (REFCL), as the best approach for the SCE distribution system. This approach uses both an Arc Suppression Coil (ASC), also known as a ground fault neutralizer (https://eepower.com/technical-articles/electrical-grounding-using-the-ground-fault-neutralizer-petersen-coil-method), to limit the current to ground in a “wire-down” scenario and Capacitive Balancing Units (CBU) on individual lines to equalize the line capacitance, a critical requirement to the REFCL solution.

 

SCE demonstrated the feasibility of the REFCL solution via testing with a manually operated prototype, but needs to operate the ASC and CBU remotely because the system response changes when their system is reconfigured. As C/P has had a history providing over 10,000 remotely-operated motor operators, SCE approached C/P to design remotely-operated ASCs and CBUs.

 

C/P worked with the SCE engineering team to design and develop the ASC and the CBU. The CBU is comprised of nine capacitors that are connected between the SCE power line and ground through a distribution transformer. Each capacitor is separately controlled and monitored, allowing SCE to increase or decrease the additional capacitance added to the distribution line and identify any capacitor damage. The capacitors can be controlled locally and remotely as needed by SCE. The ASC is comprised of five inductors connected in parallel with a similar capacitor arrangement to adjust the amount of inductance applied to the power system. Each solution required custom enclosures, wiring, and circuit boards to meet SCE’s needs.

CBU interior showing the controls and capacitor bank for line capacitance equalization. The safety guard in front of the capacitors is not shown for clarity.

1 | Local Controls
2 | Remote Control
3 | Capacitors

 

CBU interior showing the controls and capacitor bank for line capacitance equalization. The safety guard in front of the capacitors is not shown for clarity.

1 | Inductors
2 | Capacitors Behind Safe Guard

A typical CBU installation in the field.

1 | Arc Suppression Coil
2 | Output Delta Configuration
2 | Input WYE Configuration

SCE installed WYE to Delta conversion with 1:1 transformers to enable the REFCL in fire prone areas without needing to reconfigure all lines from a substation.

 

As of late 2024, SCE is in the process of installing these ASCs and CBUs on their distribution system and expects to continue the rapid deployment of these devices to reduce wildfires until at least 2030.

C/P worked with the SCE engineering team to design and develop the ASC and the CBU.