Vertical Break Switch

V2-CA

Decoration

The Cleaveland/Price V2-CA is a three pole, group operated, aluminum vertical break switch for installation in substation or transmission line locations. The switch can be mounted in the horizontal-upright, vertical, or horizontal-underhung position. The V2-CA is suitable for use in a variety of applications, including line disconnecting and sectionalizing, circuit breaker by-pass and isolation, and transformer isolation.

Arc horns or quick break whips can be supplied when small amounts of transformer magnetizing currents or line charging currents must be interrupted.

Accessories and options needed to adapt the switch to a customer’s particular requirements are available. The V2-CA may be manually operated via swing handle or wormgear mechanism, or electrically operated via type TP-C2 motor operator.

The V2-CA meets NEMA and IEEE Standards and the rating requirements of applicable IEC Standards.

Quality Construction

Decoration
  • Unbreakable, non-cast aluminum terminal pads with NEMA standard hole pattern
  • Fully insulated sleeve bearing
  • Unbreakable, non-cast operating crank
  • Insulated from the current path: counterbalance ice shields; stainless steel contact springs with lifelong corrosion resistance, and stainless steel counterbalance springs with lifelong corrosion resistance

  • Silver-to-silver contacts at hinge and jaw
  • Blade constructed of T-6063 aluminum or tin-plated copper
  • Stainless steel contact springs insulated from the current path
  • Tin-plated, hard-drawn, high conductivity copper contact fingers at hinge and jaw
  • Hot-dip galvanized double channel base
  • Insulator leveling screws

Engineered for Performance

Decoration

Cleaveland/Price has a very basic approach to design: keep it simple. It is an approach employed from material selection to mechanical design. The Cleaveland/Price V2-C disconnect switch current carrying parts are manufactured from high strength, high conductivity copper. All switches are of non-cast design for superior dependability of parts. Switch performance is not troubled by flaws that could occur in the casting process. Contacts are designed to take advantage of electromagnetic forces by using a reverse loop configuration at both the hinge and jaw of the switch. Current transfer points are kept to a minimum.

Blade Turnover

Innovation for Full Contact Pressure

Decoration

Traditional Problem

Decoration

When the blade on a conventional switch rotates to the final closed position in the break-jaw, it does not consistently stop at the point of optimum contact pressure.

 

Many switches use a stop on the rotating insulator to set the blade position in the break-jaw. This type of stop is too distant from the blade to accurately control the blade motion, due to the cumulative play of the multiple linkage points. Additionally, inconsistent operating speeds can negatively affect proper blade turnover and position in the break-jaw. These fundamental design weaknesses lead to inadequate contact pressure that eventually causes contact pitting, burning, and failure.

Innovative Solution

Decoration

Instead of locating the blade stop on the rotating insulator, the Cleaveland/Price 500 kV V2-CA blade stop is factory-machined directly into the blade at the hinge. This superior location of the blade stop removes all cumulative linkage play and ensures accurate blade rotation in the break-jaw; therefore, consistently completing the closed operation at the precise point of achieving maximum contact pressure, no matter how slow or fast the switch is operated.
The cutaway view shows how the unique Cleaveland/Price turnover stop allows the blade to rotate until the factory-machined slot in the blade engages with the hinge pin. This results in a consistent and highly accurate blade turnover angle with full contact pressure for every operation.

Patented Break-Jaw Design

Decoration

The Conventional Break-Jaw Problem

Decoration

Conventional break-jaw designs lose contact pressure during short circuits due to inferior placement of the contact springs.


The forces generated under short circuits create a side-to-side movement of the blade within the break-jaw, causing a make-and-break action between the blade and jaw contacts, resulting in arcing, pitting, and burning of the switch contacts.

The Innovative Solution by Cleaveland/Price

Decoration

The superior Cleaveland/Price 500 kV V2-CA break-jaw design maintains a constant high-contact pressure as the blade moves side-to-side and increases during short circuits by working in unison with the electromagnetic forces generated by the current path.


The ideal location and design of the contact springs join the contact fingers together, allowing the switch contacts to move side-to-side with the blade during short circuits. This floating contact spring system maintains contact spring pressure during side-to-side movement, while maintaining a constant electrical connection to ensure no arcing of contacts.

StayDry® Bearing

Decoration
The StayDry® bearing is a patented, watertight ball bearing assembly for rotating insulators on disconnect switches which provides the ultimate in reliability. The application of hydrophobic membrane technology eliminates seal stress and keeps the bearing free of water and any condensing moisture thereby preventing any corrosion. This proven technology has been used across a wide array of industries for decades to protect enclosed volumes from the effects of temperature and pressure fluctuations, moisture, and contaminants.

By the Numbers (Ratings)

Decoration
V2-CAVoltage RatingsAmperage Ratings
Catalog
Number
Nominal
Voltage (kV)
Maximum
Voltage (kV)
BIL (kV)Insulator
TR No.
Continuous
Current (A)
Peak Withstand
Current (kA)
Short-Time Withstand
Current (kA @ 3 sec.)
A0AA7.28.3952026006525
A0AB7.28.39520212009938
A0AC7.28.395202160011444
A0AD7.28.395202200016463
A0AE7.28.395202250016463
A0AF7.28.395202300019575
A0AH7.28.395202400019575
A0BA14.415.51102056006525
A0BB14.415.511020512009938
A0BC14.415.5110205160011444
A0BD14.415.5110205200016463
A0BE14.415.5110205250016463
A0BF14.415.5110205300019575
A0BH14.415.5110205400019575
A0CA23271502086006525
A0CB232715020812009938
A0CC2327150208160011444
A0CD2327150208200016463
A0CE2327150208250016463
A0CF2327150208300019575
A0CH2327150208400019575
A0DA34.5382002106006525
A0DB34.53820021012009938
A0DC34.538200210160011444
A0DD34.538200210200016463
A0DE34.538200210250016463
A0DF34.538200210300019575
A0DH34.538200210400019575
A0EA4648.32502146006525
A0EB4648.325021412009938
A0EC4648.3250214160011444
A0ED4648.3250214200016463
A0EE4648.3250214250016463
A0EF4648.3250214300019575
A0EH4648.3250214400019575
A0FA6972.53502166006525
A0FB6972.535021612009938
A0FC6972.5350216160011444
A0FD6972.5350216200016463
A0FE6972.5350216250016463
A0FF6972.5350216300019575
A0FH6972.5350216400019575
A0GA1151235502866006525
A0GB11512355028612009938
A0GC115123550286160011444
A0GD115123550286200016463
A0GE115123550286250016463
A0GF115123550286300019575
A0GH115123550286400019575
A0HA1381456502886006525
A0HB13814565028812009938
A0HC138145650288160011444
A0HD138145650288200016463
A0HE138145650288250016463
A0HF138145650288300019575
A0HH138145650288400019575
A0JA1611707502916006525
A0JB16117075029112009938
A0JC161170750291160011444
A0JD161170750291200016463
A0JE161170750291250016463
A0JF161170750291300019575
A0JH161170750291400019575
A0KA2302459003046006525
A0KB23024590030412009938
A0KC230245900304160011444
A0KD230245900304200016463
A0KE230245900304250016463
A0KF230245900304300019575
A0KH230245900304400019575
A0KA23024510503126006525
A0KB230245105031212009938
A0KC2302451050312160011444
A0KD2302451050312200016463
A0KE2302451050312250016463
A0KF2302451050312300019575
A0KH2302451050312400019575

Vertical Break

Superior Reliability and Dependability.

Decoration

Quality materials are the foundation of any reliable disconnect switch. Made from high-quality materials, Cleaveland/Price vertical switches feature an all non-cast design, reducing potential casting defects and enhancing long-term dependability.

Aluminum

Copper

High Current

U Terminal

Extra High Voltage