MOTOR OPERATORS

TP-C3

Decoration

The Cleaveland/Price TP-C3 is a heavy-duty motor operating mechanism designed to operate disconnect switches requiring torsional motion. The TP-C3 uses a permanent magnet motor to enable higher torques while still providing all the functionality and modularity of the TP-C2 motor operator.

The TP-C3 is built on the knowledge gained from 30 years of manufacturing the TP-C2. All the features that have made the TP-C2 successful have been transferred to the TP-C3. This motor operator enables remote, local, and manual operation of the disconnect switch and easily mounts to any structure. The TP-C3 interior design allows access to all components through the enclosure door, and all internal items are factory wired for ease of installation. The auxiliary switch has been relocated to front of the cabinet to allow easy modifications of travel limits.

A higher horsepower permanent magnet motor will draw more current from the power source: the TP-C3 control board is designed to use solid-state controls and transistor interruption to switch up to a 125 AMP current.

Alternate Configurations

Decoration

The TP-C3 is used in applications that require less than one rotation of the operating pipe.

  • TP-C3M – For switches that require multiple rotations of the operating pipe.
TP-C3 Numbered

TP-C3 Operator Features

Decoration
  1. Provision for swing handle operation
  2. Torque relief decoupler
  3. Provisions for padlocking the high voltage switch in position
  4. NEMA 3R powder coated aluminum enclosure
  5. Stainless steel door hinge, stop, and lockable handle
  6. Fully gasketed enclosure
  7. Removable conduit plate
  8. Local operational controls
  9. Auxiliary Switch
  10. Handcrank

Internal Features

Decoration

Control Circuit
C/P substation class motor operators utilize an advanced control circuit design. Mechanical relays are not used to interrupt motor current. Power interruption is by solid state components with a mechanical relay in series that provides the assurance of an open circuit. Heavy arcing on relay contacts is eliminated—a proven breakthrough for long-term performance. The control circuit provides a seal-in feature, as well as electrically interlocked directional relays. The circuit is intrinsically safe with no possibility of two contacts closing at the same time.

Motor

The operator utilizes either a maintenance-free universal motor in the TP-C2 or a permanent magnet motor in the TP-C3. Motor overload protection is provided by a fuse. A circuit breaker and thermal overload relay are available as options. Operating personnel are protected from the chain and sprocket drive mechanism by the removable front panel.

Drive Mechanism

A combination chain drive and wormgear are used to power the output shaft. The chain driven wormgear mechanism is superior to spur gear mechanisms during heavy ice duty.

Braking
The motor operator uses a dynamic braking system to provide ultra-precise, repeatable, service-free braking action. Braking is initiated by either limit switches or the stop button. With the dynamic braking system, there is no brake shoe or solenoid maintenance. Back-travel of the vertical operating pipe is prevented by the high ratio wormgear drive, which effectively locks the switch in the open and closed positions.

Standard Features

Decoration
  • Torque relief decoupler
  • Powder coated aluminum NEMA 3R enclosure
  • Thermostatically controlled heater
  • Dynamic braking for motor stopping
  • Two auxiliary switches for customer use
  • Hand crank for manual operation

Optional Features

Decoration
  • Operations counter
  • Variable Speed Control (see below)
  • Local Operation Delay (see below)
  • Position indicator lights
  • Stainless steel enclosure
  • Swing handle for ice breaking

Variable Speed Control

Decoration

High voltage switches may draw a large arc when closing in the presence of a magnetizing or line charging current. To minimize this arcing, the switch must be closed quickly until the arc horn makes contact, but this speed needs reduced immediately to prevent switch blade damage. Variable Speed Control allows adjustment of switch blade speed during opening and closing.

Local Operation Delay

Decoration

When operating locally, the time delay helps protect utility personnel by allowing them to reach a safe distance before the switch operates. C/P substation motor operators can be equipped with a time delay module that is integrated into the front panel and can be set from 0 to 99 seconds.

By the Numbers (Ratings)

Decoration
Control/Motor VoltageOutput Torque (in-lbs)Operating Time (180°)Locked Rotor Torque (A)Schematic DiagramWiring DiagramOutline Number
125VDC30,00011.0s70C311A007C311A008C15B003G001
120VAC30,00011.0s45C311A011C311A012C15B003G003
240VAC30,00011.0s25C311A015C311A016C15B003G005

Motor Operators and Controllers

Superior Reliability Through Design

Decoration

In everyday switching operations or emergency situations, a motor operator must operate when needed. Cleaveland/Price Inc. has been manufacturing motor operators since the 1990s and has developed field proven and reliable devices that give you the confidence that the motor will operate the switch when called upon. With thousands of installations throughout North America, Cleaveland/Price motor operators and controllers have demonstrated their dependability in a wide variety of environments and applications.