The Cleaveland/Price TP-C2 is a motor operating mechanism designed to operate disconnect switches requiring torsional motion. The TP-C2 enables remote control of the disconnect switch as well as local electrical and manual operation. Manual operation is by handcrank or optional swing handle. The TP-C2 easily mounts to any structure and is interchangeable with the Cleaveland/Price geared handcrank operator.

The TP-C2 is the result of years of experience and user input  and incorporates improvements and features most desired by the electrical power industry. The motor operator is simple and user friendly. All internal components of the motor operator are accessible through the front door, eliminating the need for removable side panels. The motor control circuit, auxiliary switches, and heater are factory wired to terminal blocks located at the front of the operator enclosure. Overcurrent protection for the motor and heater are conveniently located at the front of the enclosure.

The solid-state controls switch heavy DC motor currents without eroding of relay contacts. The solid-state controls are connected through heavy-duty pin connectors, allowing quick changing of any component.

Alternate Configurations

Decoration

The TP-C2 is designed for substation switches requiring torsional motion. Cleaveland Price also offers variants of this design for specific applications:

  • TP-D2 – For distribution switches that require torsional motion and are installed inside of the substation fence. These motor operators operate faster than a TP-C2.
  • TP-T2 – For switches powered by station batteries but installed outside of the substation fence. These motor operators have a decoupler guard for additional tamper-proof security.

TP-C2 Operator Features

Decoration
  1. Provision for swing handle operation
  2. Torque relief decoupler
  3. Provisions for padlocking the high voltage switch in position
  4. NEMA 3R powder coated aluminum enclosure
  5. Stainless steel door hinge, stop, and lockable handle
  6. Fully gasketed enclosure
  7. Removable conduit plate
  8. Local operational controls
  9. Auxiliary Switch
  10. Handcrank

Internal Features

Decoration

Control Circuit
C/P substation class motor operators utilize an advanced control circuit design. Mechanical relays are not used to interrupt motor current. Power interruption is by solid state components with a mechanical relay in series that provides the assurance of an open circuit. Heavy arcing on relay contacts is eliminated—a proven breakthrough for long-term performance. The control circuit provides a seal-in feature, as well as electrically interlocked directional relays. The circuit is intrinsically safe with no possibility of two contacts closing at the same time.

Motor

The operator utilizes either a maintenance-free universal motor in the TP-C2 or a permanent magnet motor in the TP-C3. Motor overload protection is provided by a fuse. A circuit breaker and thermal overload relay are available as options. Operating personnel are protected from the chain and sprocket drive mechanism by the removable front panel.

Drive Mechanism

A combination chain drive and wormgear are used to power the output shaft. The chain driven wormgear mechanism is superior to spur gear mechanisms during heavy ice duty.

Braking
The motor operator uses a dynamic braking system to provide ultra-precise, repeatable, service-free braking action. Braking is initiated by either limit switches or the stop button. With the dynamic braking system, there is no brake shoe or solenoid maintenance. Back-travel of the vertical operating pipe is prevented by the high ratio wormgear drive, which effectively locks the switch in the open and closed positions.

Standard Features

Decoration
  • Torque relief decoupler
  • Powder coated aluminum NEMA 3R enclosure
  • Thermostatically controlled heater
  • Dynamic braking for motor stopping
  • Two auxiliary switches for customer use
  • Hand crank for manual operation

Optional Features

Decoration
  • Operations counter
  • Variable Speed Control (see below)
  • Local Operation Delay (see below)
  • Position indicator lights
  • Stainless steel enclosure
  • Swing handle for ice breaking

Variable Speed Control

Decoration

High voltage switches may draw a large arc when closing in the presence of a magnetizing or line charging current. To minimize this arcing, the switch must be closed quickly until the arc horn makes contact, but this speed needs reduced immediately to prevent switch blade damage. Variable Speed Control allows adjustment of switch blade speed during opening and closing.

Local Operation Delay

Decoration

When operating locally, the time delay helps protect utility personnel by allowing them to reach a safe distance before the switch operates. C/P substation motor operators can be equipped with a time delay module that is integrated into the front panel and can be set from 0 to 99 seconds.

By the Numbers (Ratings)

Decoration
Control/Motor VoltageOutput Torque (in-lbs)Operating Time (180°)Locked Rotor Torque (A)Schematic DiagramWiring DiagramOutline Number
24VDC20,0005.4s150C211B003C211B004C15A005G002
24VDC20,00011.0s150C211B003C211B004C15A005G003
48VDC20,0005.4s95C211B005C211B006C15A004G002
48VDC20,00011.0s95C211B005C211B006C15A004G003
125VDC20,0005.4s35C311A005C311A006C15A001G002
125VDC20,00011.0s35C311A005C311A006C15A001G003
250VDC20,0005.4s11C211B007C211B008C15A006G002
250VDC20,00011.0s11C211B007C211B008C15A006G003
120VAC10,0005.4s20C311A009C311A010C15A002G001
120VAC15,000*5.1s20C311A009C311A010C15A002G002
120VAC20,00011.0s20C311A009C311A010C15A002G003
240VAC10,0005.4s10C311A013C344A014C15A003G001
240VAC15,000*5.1s10C311A013C344A014C15A003G002
240VAC20,00011.0s10C311A013C344A014C15A003G003

Motor Operators and Controllers

Superior Reliability Through Design

Decoration

In everyday switching operations or emergency situations, a motor operator must operate when needed. Cleaveland/Price Inc. has been manufacturing motor operators since the 1990s and has developed field proven and reliable devices that give you the confidence that the motor will operate the switch when called upon. With thousands of installations throughout North America, Cleaveland/Price motor operators and controllers have demonstrated their dependability in a wide variety of environments and applications.

Substation

Distribution

Transmission