DISTRIBUTION MOTOR OPERATOR
PAD
The PAD Motor Operator is used to automate padmounted switches. The motor operator opens and closes the switch with an operating time of 12 seconds with a torque of 3000 in-lbs. Other operating times and torques are available upon request.
PAD Motor Operators mount easily to the customer’s padmounted switch without the need for field drilling or switch enclosure modification. The mechanism can be installed in minutes: no need to take the switch out of service during installation.
PAD Motor Operator Features
- Decoupler
- Padlockable motor assembly
- NEMA 3R powder coated aluminum enclosure
- Fully gasketed enclosure
- Local operational controls
- Manual handle
- Battery
- Control electronics
- Stainless steel door hinge, stop, and handle
- Provisions for RTU and radio
- Removable access plate
Power Train
The PAD motor operator is driven by a 24V permanent magnet motor. A dynamic braking circuit is used to provide an extremely precise stopping point in both the open and closed positions. The braking action is initiated by a programmable front panel at the ends of travel. The PAD motor operator utilizes a gear driven mechanism that has limits of travel set at the front panel rather than limit switches inside the motor.
Battery
The battery used in the motor operator an SLA (sealed lead-acid) type. The battery typically has a 4–5 year life, depending upon duty and environment. In regions with sustained high temperatures, the life of the battery may be extended through use of the Cleaveland/Price battery cooler accessory that provides an optimal constant temperature environment. It has a pressure relief valve that only opens during excessive gas buildup. Gasses are vented via a hose to the outside of the enclosure, preventing the buildup of corrosive and explosive gasses within the enclosure.
Battery and Charging
All motor operators utilize a 12V 33AH battery that is charged by a transformer. The battery charger is temperature compensated so that the battery always receives the proper charging voltage. The battery can operate a switch over 100 times on a full charge and can keep the PAD powered for up to 72 hours after loss of charging power. The battery charger provides several status points that are reported to the supervisor system that alert the utility of battery condition. That battery condition is provided in real time with the battery automatically checked every five minutes to ensure that you have an accurate date battery health indicator.
Operation
Operations can be initiated locally, remotely, or manually. Local operations are performed via the front panel, remote operations occur via communication device and remote terminal unit (RTU) contact closure, and manual operations are completed with a manual handle.
Motor operators run the motor from the 120V feed as the primary power source and uses the 12V battery as a backup. Because the motor operator uses AC as its primary power source, the motor operator will run if AC is present even if the battery is weak. AC and battery power are supplied to the motor concurrently. This means the motor operator will complete an operation without hesitation, even if AC is lost during the operation (such as having the distribution transformer on the load side of the switch).
The motor operator incorporates a stall timer that automatically terminates motor operation after a predefined time interval. If the motor operator stalls due to switch icing or a mechanical obstruction, the timer ends the operation before prolonged stall current can cause the DC fuse to open. This feature helps prevent the unit from becoming inoperable and reduces the need for field service associated with fuse replacement.
Enclosure and Wiring
The motor operator enclosure offers sufficient room to house most RTUs and radios with all components being accessible through the front door. The unit mounts easily to any manufacturer’s pad mounted switch without any field drilling of the switch. Refer to the chart below detailing common switch manufacturers, and contact C/P if you have a switch that isn’t listed. The enclosure is powder coated green to best match typical PAD mounted switchgear. If custom colors are required, C/P can powder coat in any color necessary.
Cleaveland Price can factory install radios, RTU, sensors, relays, and any other specialty device. When installed at the C/P factory, our production team will verify the functionality of each device, ensuring that the motor operator requires minimal field installation time.
By the Numbers (Ratings)
| Battery Charger Voltage | Output Torque (in-lbs) | Operating Time (180°) | Schematic Diagram | Wiring Diagram | Outline Number |
|---|---|---|---|---|---|
| 120VAC | 3,000 | 4 seconds | C128B996 | N/A | CB33AA03 |
Mounting Kits
| Switch type | Mounting Kit |
|---|---|
| S&C | C132A036 |
| Federal Pacific | C133A004 |
| Hubbell | C132A033 |
| Shallbetter | C132A833 |
Motor Operators and Controllers
Superior Reliability Through Design
In everyday switching operations or emergency situations, a motor operator must operate when needed. Cleaveland/Price Inc. has been manufacturing motor operators since the 1990s and has developed field proven and reliable devices that give you the confidence that the motor will operate the switch when called upon. With thousands of installations throughout North America, Cleaveland/Price motor operators and controllers have demonstrated their dependability in a wide variety of environments and applications.