DISTRIBUTION MOTOR OPERATOR
PTAD
The PTAD motor operator prevents the issue of distribution switches going out of adjustment (due to pole twisting, aging, or humidity) as it mounts the motor assembly directly on the switch crossarm. The control enclosure is installed at ground level and connects to the motor assembly by a control cable. This configuration allows the control enclosure to be mounted anywhere on the pole rather than directly beneath the switch or requiring multiple universal joints.
PTAD Motor Operator Features
- Electrical lockout
- NEMA 3R powder coated aluminum enclosure
- Fully gasketed enclosure
- Local operational controls
- Control electronics
- Stainless steel door hinge, stop, and handle
- Provisions for RTU and radio
- Removable access plate
- Battery
PTAD Motor Features
10. Hotstick operation lever
11. Cross arm mounting bracket
12. Hotstickable mechanical lockout
13. Switch drive lever
Power Train
The PTAD Motor Operator is driven by a universal, AC/DC reversible series-wound motor. The maintenance-free motor is rated ¾ horsepower. The crossarm mounted motor assembly utilizes a solenoid engaged chain driven mechanism that decouples from the switch after every operation, allowing hookstick operation without any additional steps. Travel limits are set by selecting the type of switch in the linkage, so there are no limit switches to set.
Battery
The battery used in the motor operator is an SLA (sealed lead-acid) type. The battery typically has a 4–5 year life, depending upon duty and environment. In regions with sustained high temperatures, the life of the battery may be extended through use of the Cleaveland/Price battery cooler accessory that provides an optimal constant temperature environment. It has a pressure relief valve that only opens during excessive gas buildup. Gasses are vented via a hose to the outside of the enclosure, preventing the buildup of corrosive and explosive gasses within the enclosure.
Battery and Charging
All motor operators utilize a 12V 33AH battery that is charged by a transformer or solar panels. The battery charger is temperature compensated so that the battery always receives the proper charging voltage. The battery can operate a switch over 100 times on a full charge and keep the BT-D powered for up to 72 hours after loss of charging power. The battery charger provides several status points that are reported to the supervisor system that alert the utility of battery condition. That battery condition is provided in real time with the battery automatically checked every five minutes to ensure that you have an accurate date battery health indicator.
Solar installations require solar panels, mounting, and additional batteries. Cleaveland Price can assist with engineering the quantities of each and provide a complete solution including all required parts.
Operation
Operations can be initiated locally, remotely, or manually. Local operations are performed via the front panel, remote operations occur via communication device and remote terminal unit (RTU) contact closure, and manual operations are completed with a manual handle.
Motor operators run the motor from the 120V feed as the primary power source and uses the 12V battery as a backup. Because the motor operator uses AC as its primary power source, the motor operator will run if AC is present even if the battery is weak. AC and battery power are supplied to the motor concurrently. This means the motor operator will complete an operation without hesitation, even if AC is lost during the operation (such as having the distribution transformer on the load side of the switch).
The motor operator incorporates a stall timer that automatically terminates motor operation after a predefined time interval. If the motor operator stalls due to switch icing or a mechanical obstruction, the timer ends the operation before prolonged stall current can cause the DC fuse to open. This feature helps prevent the unit from becoming inoperable and reduces the need for field service associated with fuse replacement.
Enclosure and Wiring
The motor operator enclosure offers sufficient room to house most RTUs and radios with all components accessible through the front door. The unit mounts easily to wood, steel, or concrete poles and can be installed at any height on the pole. The enclosure is powder coated white to provide a surface that reflects the heating rays of the sun, thereby reducing heat buildup within the enclosure increasing the lifetime of the battery.
Cleaveland/Price can factory install radios, RTU units, sensors, relays, and any other specialty device. When installed at the C/P factory, our production team will verify the functionality of each device, ensuring that the motor operator requires minimal field installation time.
By the Numbers (Ratings)
| Battery Charger Voltage | Motor Output Torque | Operating Time 90° | Schematic Diagram | Wiring Diagram | Outline Number |
|---|---|---|---|---|---|
| 120VAC | 7,500 in-lb | 0.4 seconds | C128B995 | C138B001 | CB38AA03G001 |
Switch Kit Information
| Switch Manufacturer | Switch Style | Mounting Orientation | Voltage Rating (kV) | Mounting Kit |
|---|---|---|---|---|
| Siemens | Vector (150kV BIL) | Horizontal | 25 / 38 | CB38BD01 |
| Siemens | Vector (150kV BIL) | Phase over Phase | 25 | CB38BD02 |
| Cooper | M-Force | Horizontal | 38 | CB38CQ01 |
| Cooper | M-Force | Phase over Phase | 38 | CB38CQ02 |
| Cooper | M-Force | Horizontal | 15 / 25 | CB38CQ03 |
| Hubbell | AR / D& (150kV BIL) | Horizontal | 15 / 25 / 35 | CB38HB01 |
| Hubbell | AR | Vertical | 15 / 25 / 35 | CB38HB02 |
| Hubbell | D7 (200kV BIL) | Horizontal | 35 | CB38HB03 |
| Hubbell | AR | Phase over Phase | 15 / 25 / 35 | CB38HB05 |
| Hubbell | D7 | Phase over Phase | 25 | CB38HB06 |
| S&C | Omnirupter | Horizontal | 15 / 25 | SB38SZ01 |
| S&C | Omnirupter | Vertical | 15 / 25 | SB38SZ02 |
| S&C | Omnirupter | Phase over Phase | 15 / 25 | SB38SZ03 |
| S&C | Alduti | Horizontal | 15 / 25 | SB38SZ04 |
| S&C | Alduti | Horizontal | 15 / 25 | SB38SZ05 |
| Intertia | LineBOSS | Horizontal | 25 | CB38NR01 |
| Intertia | LineBOSS | Vertical | 25 | CB38NR02 |
| Intertia | LineBOSS | Underarm | 25 | CB38NR03 |
Motor Operators and Controllers
Superior Reliability Through Design
In everyday switching operations or emergency situations, a motor operator must operate when needed. Cleaveland/Price Inc. has been manufacturing motor operators since the 1990s and has developed field proven and reliable devices that give you the confidence that the motor will operate the switch when called upon. With thousands of installations throughout North America, Cleaveland/Price motor operators and controllers have demonstrated their dependability in a wide variety of environments and applications.