Center Break Switch
CB-CV
The Cleaveland/Price CB-CV switch is a three pole, group operated, copper center break switch for substation installations. The switch is suitable for use in a variety of applications including line disconnecting, circuit breaker bypass and isolation, and transformer isolation. The switch may be manually operated by use of a swing handle or wormgear mechanism or electrically operated by a type TP-C2 motor operator.
The CB-C switch has parallel insulators and may be mounted in the horizontal upright, vertical, or horizontal underhung position.
Accessories and options needed to adapt the switch to a customer’s particular requirements are available. Arc horns or quick break whips can be supplied when small amounts of transformer magnetizing currents or line charging currents must be interrupted.
The CB-C switch is designed to meet applicable NEMA and IEEE Standards and the rating requirements of applicable IEC Standards.
Quality Construction
The CB-CV continues the Cleaveland/Price tradition of designing simple, dependable switches without the use of castings. Knowledge gained from maintaining switches in the field for over 60 years has played a major part in refining the CB-CV. Significant design features include:
- Total non-cast copper and steel parts resulting in superior dependability of parts
- Live parts constructed from hard-drawn, high conductivity copper, producing stronger, more conductive components than parts made of cast materials
- High-pressure line contacts for effective transfer current
- Wiping action at the jaw contacts keep the contacts clean for years of reliable service. Contacts have a long wipe surface to accommodate insulator movement.
- Simple inter-insulator linkage.
- Rigid base assembly
By the Numbers (Ratings)
| CB-CV | Voltage Ratings | Amperage Ratings | |||||
|---|---|---|---|---|---|---|---|
| Catalog Number | Nominal Voltage (kV) | Maximum Voltage (kV) | BIL (kV) | Insulator TR No. | Continuous Current (A) | Peak Withstand Current (kA) | Short-Time Withstand Current (kA @ 3 sec.) |
| CTBB | 14.4 | 15.5 | 110 | 205 | 1200 | 99 | 38 |
| CTBD | 14.4 | 15.5 | 110 | 205 | 2000 | 164 | 63 |
| CTCB | 23 | 27 | 150 | 208 | 1200 | 99 | 38 |
| CTCD | 23 | 27 | 150 | 208 | 2000 | 164 | 63 |
| CTDB | 34.5 | 38 | 200 | 210 | 1200 | 99 | 38 |
| CTDD | 34.5 | 38 | 200 | 210 | 2000 | 164 | 63 |
| CTEB | 46 | 48.3 | 250 | 214 | 1200 | 99 | 38 |
| CTED | 46 | 48.3 | 250 | 214 | 2000 | 164 | 63 |
| CTFB | 69 | 72.5 | 350 | 216 | 1200 | 99 | 38 |
| CTFD | 69 | 72.5 | 350 | 216 | 2000 | 164 | 63 |



