INDOOR DISCONNECT SWITCH
LCG-CD
The LCG-CD is a three-phase, group-operated disconnect switch designed for isolation in segregated and non-segregated bus systems. Its double-throw design includes a second pole that is permanently connected to ground. As the switch moves from the energized position to the grounded position, the blades disconnect the circuit from the energized pole and then connect the isolated circuit and downstream equipment to ground.
LCG-CD switches are not designed to make or break load current and do not have fault-closing capability. They are available at voltage ratings from 5 kV through 34.5 kV and continuous-current ratings up to 2,000 A. The design reflects the Cleaveland/Price emphasis on simplicity and reliability. All three phases are unitized; factory-assembled on a common base to simplify installation.
LCG-CD switches feature no cast parts for superior dependability. All current carrying parts are fabricated from hard-drawn, high-conductivity copper. The silver-to-silver contacts are backed by stainless steel conical springs. The switches are typically supplied with wet process porcelain insulators.
The switch may be operated by a chain-drive operator, side handle, or motor operator. Operator selection depends on the switch rating, mounting height, and available clearance. All operating devices are padlockable and include provisions for mounting keyed interlocks.
Quality Construction
- All Copper Current Carrying Live Parts
- All Stainless-Steel Hardware
- Galvanized Steel Switch Bases
- Porcelain Insulators
- Designed, Fabricated, and Assembled in the USA
Automatically Grounding Disconnect Switch Features
- Hot-dip galvanized steel frame.
- High strength torsional drive shaft.
- Track resistant drive link.
- Permanently lubricated, maintenance-free journal bearings.
- High strength hard drawn copper terminal pads. Available with NEMA standard hole patterns.
- High pressure silver-to-silver line contacts at the hinge contact.
- High strength hard drawn copper blades.
- High conductivity silver-to-silver contacts at the hinge and jaw.
- Optional integral interphase arc barriers reduce phase spacing if required. Barriers mount to the switch base not the enclosure simplifying installation.
- Automatic integral grounding in the open position.
By the Numbers (Ratings)
| LCG-CD | Voltage Ratings | Amperage Ratings | |||||
|---|---|---|---|---|---|---|---|
| Catalog | Nominal | Maximum | BIL (kV) | Insulator | Continuous | Peak Withstand | Short-Time Withstand |
| Number | Voltage (kV) | Voltage (kV) | TR No. | Current (A) | Current (kA) | Current (kA @ 3 sec.) | |
| S0UA | 4.16 | 4.8 | 60 | A20 | 600 | 65 | 25 |
| S0UB | 4.16 | 4.8 | 60 | A20 | 1200 | 99 | 38 |
| S0UD | 4.16 | 4.8 | 60 | A20 | 2000 | 130 | 50 |
| S0VA | 7.2 | 8.25 | 75 | A20 | 600 | 65 | 25 |
| S0VB | 7.2 | 8.25 | 75 | A20 | 1200 | 99 | 38 |
| S0VD | 7.2 | 8.25 | 75 | A20 | 2000 | 130 | 50 |
| S0WA | 12 | 15.5 | 95 | A20 | 600 | 65 | 25 |
| S0WB | 12 | 15.5 | 95 | A20 | 1200 | 99 | 38 |
| S0WD | 12 | 15.5 | 95 | A20 | 2000 | 130 | 50 |
| S0XA | 12 | 15.5 | 110 | A20 | 600 | 65 | 25 |
| S0XB | 12 | 15.5 | 110 | A20 | 1200 | 99 | 38 |
| S0XD | 12 | 15.5 | 110 | A20 | 2000 | 130 | 50 |
| S0XE | 12 | 15.5 | 110 | A30 | 3000 | 164 | 75 |
| S0YA | 23 | 27 | 125 | A20 | 600 | 65 | 25 |
| S0YB | 23 | 27 | 125 | A20 | 1200 | 99 | 38 |
| S0YD | 23 | 27 | 125 | A20 | 2000 | 130 | 50 |
| S0ZA | 34.5 | 38 | 150 | A30 | 600 | 65 | 25 |
| S0ZB | 34.5 | 38 | 150 | A30 | 1200 | 99 | 38 |
| S0ZD | 34.5 | 38 | 150 | A30 | 2000 | 130 | 50 |
Metal Enclosed - In-Line
Superior Reliability Through Design
With a 50-year proven track record, these switches are bulletproof for demanding indoor/enclosed power applications. They are USA made with hard drawn and extruded materials instead of castings for exceptional short circuit performance and long-term reliability.