EHV Double Break
DB-A | DB-AV
The Cleaveland/Price 345 kV DB-A is an aluminum double break switch that continues the Cleaveland/Price tradition of manufacturing reliable, low-maintenance, non-cast switches. It is available in a traditional parallel insulator configuration, as well as a low-profile “V” configuration.
In application, the double break switch design is interchangeable with the vertical break as it can be installed on the same phase spacing. An advantage of a double break over a vertical break is that overhead clearance is less of a consideration because the blade operates in a horizontal plane. The blades are naturally counterbalanced so a counterbalance mechanism is unnecessary.
The Cleaveland/Price DB-A switch design features a patented blade rotation mechanism. The bearings for blade roll-over are adjacent to the blade and offset from the blade’s rotational axis rather than around the outer surface of the blade. This allows the bearings to be a very small diameter, which greatly reduces the force needed to operate the switch.
The mechanism also utilizes the weight of the blade pivoting on the offset bearings to assist in opening the switch. DB-A contacts are designed to take advantage of electromagnetic forces by using a reverse-loop configuration at the breakjaws. Current transfer points are kept to a minimum.
The DB-A and DB-AV meet applicable NEMA and IEEE Standards and the rating requirements of applicable IEC Standards. Testing included short circuit, temperature rise, dielectric, mechanical endurance, ice, corona, and radio influence voltage.
Quality Construction
Total non-cast construction results in superior dependability of parts:
- Hard-drawn, high conductivity copper produces stronger, more conductive live components than parts made of cast materials.
- Wiping action on the break-jaw keeps contacts clean for years of reliable service.
- Parallel blade construction allows free flow of air over the blade surfaces for efficient cooling.
- Built-in closed position blade stop on the live parts prevents over-travel on the blade.
DB-ABy the Numbers (Ratings)
| DB-A | Voltage Ratings | Amperage Ratings | |||||
|---|---|---|---|---|---|---|---|
| Catalog Number | Nominal Voltage (kV) | Maximum Voltage (kV) | BIL (kV) | Insulator TR No. | Continuous Current (A) | Peak Withstand Current (kA) | Short-Time Withstand Current (kA @ 3 sec.) |
| HAAA | 7.2 | 8.3 | 95 | 202 | 600 | 65 | 25 |
| HAAB | 7.2 | 8.3 | 95 | 202 | 1200 | 99 | 38 |
| HAAC | 7.2 | 8.3 | 95 | 202 | 1600 | 114 | 44 |
| HAAD | 7.2 | 8.3 | 95 | 202 | 2000 | 164 | 63 |
| HABA | 14.4 | 15.5 | 110 | 205 | 600 | 65 | 25 |
| HABB | 14.4 | 15.5 | 110 | 205 | 1200 | 99 | 38 |
| HABC | 14.4 | 15.5 | 110 | 205 | 1600 | 114 | 44 |
| HABD | 14.4 | 15.5 | 110 | 205 | 2000 | 164 | 63 |
| HACA | 23 | 27 | 150 | 208 | 600 | 65 | 25 |
| HACB | 23 | 27 | 150 | 208 | 1200 | 99 | 38 |
| HACC | 23 | 27 | 150 | 208 | 1600 | 114 | 44 |
| HACD | 23 | 27 | 150 | 208 | 2000 | 164 | 63 |
| HADA | 34.5 | 38 | 200 | 210 | 600 | 65 | 25 |
| HADB | 34.5 | 38 | 200 | 210 | 1200 | 99 | 38 |
| HADC | 34.5 | 38 | 200 | 210 | 1600 | 114 | 44 |
| HADD | 34.5 | 38 | 200 | 210 | 2000 | 164 | 63 |
| HAEA | 46 | 48.3 | 250 | 214 | 600 | 65 | 25 |
| HAEB | 46 | 48.3 | 250 | 214 | 1200 | 99 | 38 |
| HAEC | 46 | 48.3 | 250 | 214 | 1600 | 114 | 44 |
| HAED | 46 | 48.3 | 250 | 214 | 2000 | 164 | 63 |
| HAFA | 69 | 72.5 | 350 | 216 | 600 | 65 | 25 |
| HAFB | 69 | 72.5 | 350 | 216 | 1200 | 99 | 38 |
| HAFC | 69 | 72.5 | 350 | 216 | 1600 | 114 | 44 |
| HAFD | 69 | 72.5 | 350 | 216 | 2000 | 164 | 63 |
| HAGA | 115 | 123 | 550 | 286 | 600 | 65 | 25 |
| HAGB | 115 | 123 | 550 | 286 | 1200 | 99 | 38 |
| HAGC | 115 | 123 | 550 | 286 | 1600 | 114 | 44 |
| HAGD | 115 | 123 | 550 | 286 | 2000 | 164 | 63 |
| HAHA | 138 | 145 | 650 | 288 | 600 | 65 | 25 |
| HAHB | 138 | 145 | 650 | 288 | 1200 | 99 | 38 |
| HAHC | 138 | 145 | 650 | 288 | 1600 | 114 | 44 |
| HAHD | 138 | 145 | 650 | 288 | 2000 | 164 | 63 |
| HAJA | 161 | 170 | 750 | 291 | 600 | 65 | 25 |
| HAJB | 161 | 170 | 750 | 291 | 1200 | 99 | 38 |
| HAJC | 161 | 170 | 750 | 291 | 1600 | 114 | 44 |
| HAJD | 161 | 170 | 750 | 291 | 2000 | 164 | 63 |
| HAKA | 230/900 | 245 | 900 | 304 | 600 | 65 | 25 |
| HAKB | 230/900 | 245 | 900 | 304 | 1200 | 99 | 38 |
| HAKC | 230/900 | 245 | 900 | 304 | 1600 | 114 | 44 |
| HAKD | 230/900 | 245 | 900 | 304 | 2000 | 164 | 63 |
| HALA | 230/1050 | 245 | 1050 | 312 | 600 | 65 | 25 |
| HALB | 230/1050 | 245 | 1050 | 312 | 1200 | 99 | 38 |
| HALC | 230/1050 | 245 | 1050 | 312 | 1600 | 114 | 44 |
| HALD | 230/1050 | 245 | 1050 | 312 | 2000 | 164 | 63 |
| HAND | 345 | 362 | 1300 | 324 | 2000 | 164 | 63 |
| HANF | 345 | 362 | 1300 | 324 | 3000 | 195 | 75 |
DB-VA By the Numbers (Ratings)
| DB-AV | Voltage Ratings | Amperage Ratings | |||||
|---|---|---|---|---|---|---|---|
| Catalog Number | Nominal Voltage (kV) | Maximum Voltage (kV) | BIL (kV) | Insulator TR No. | Continuous Current (A) | Peak Withstand Current (kA) | Short-Time Withstand Current (kA @ 3 sec.) |
| H2LJ | 230 | 245 | 1050 | 312 | 5000 | 195 | 75 |
| H2NJ | 345 | 362 | 1300 | 324 | 5000 | 195 | 75 |
| H2ND | 345 | 362 | 1300 | 324 | 2000 | 164 | 63 |
| H2NF | 345 | 362 | 1300 | 324 | 3000 | 195 | 75 |