DISTRIBUTION MOTOR OPERATOR

BR

Decoration

The BR motor operator is used to automate distribution switches that operate with a reciprocating motion of the vertical operating pipe. The motor operator opens and closes the switch with an operating time of 0.4 seconds with a thrust of 800 in-lbs. Other operating times and thrusts are available upon request.

The BR motor operator is driven by a universal, AC/DC reversible series-wound motor. The maintenance-free motor is rated ¾ horsepower. A dynamic braking circuit is used to provide an extremely precise stopping point in both the open and closed positions. The braking action is initiated by two limit switches in the auxiliary switch assembly. The BR motor operator utilizes a four-bar linkage located inside the motor operator for pure reciprocating motion.

BR Motor Operator Features

Decoration
  1. Provisions for padlocking the high voltage switch in position
  2. Provisions for pump handle operation
  3. NEMA 3R powder coated aluminum enclosure
  4. Fully gasketed enclosure
  5. Local operational controls
  6. Auxiliary switch
  7. Pump handle
  8. Battery
  9. Control electronics
  10. Stainless steel door hinge, stop, and handle
  11. Provisions for RTU and radio
  12. Removable access plate

Power Train

Decoration

The motor operator is driven by a universal, AC/DC series reversible motor. The maintenance-free motor is rated ¾ horsepower. A dynamic braking circuit is used to provide an extremely precise stopping point in both the open and closed positions. The braking action is initiated by two limit switches in the auxiliary switch assembly.

The BR Motor Operator utilizes a four-bar linkage located inside the motor operator for pure reciprocating motion.

Battery

Decoration

The battery used in the motor operator is an SLA (sealed lead-acid) type. The battery typically has a 4–5 year life, depending upon duty and environment. In regions with sustained high temperatures, the life of the battery may be extended through use of the Cleaveland/Price battery cooler accessory that provides an optimal constant temperature environment. It has a pressure relief valve that only opens during excessive gas buildup. Gasses are vented via a hose to the outside of the enclosure, preventing the buildup of corrosive and explosive gasses within the enclosure. 

Battery and Charging

Decoration

All motor operators utilize a 12V 33AH battery that is charged by a transformer or solar panels. The battery charger is temperature compensated so that the battery always receives the proper charging voltage. The battery can operate a switch over 100 times on a full charge and keep the BT-D powered for up to 72 hours after loss of charging power. The battery charger provides several status points that are reported to the supervisor system that alert the utility of battery condition. That battery condition is provided in real time with the battery automatically checked every five minutes to ensure that you have an accurate date battery health indicator.

Solar installations require solar panels, mounting, and additional batteries. Cleaveland Price can assist with engineering the quantities of each and provide a complete solution including all required parts.

Operation

Decoration

Operations can be initiated locally, remotely, or manually. Local operations are performed via the front panel, remote operations occur via communication device and remote terminal unit (RTU) contact closure, and manual operations are completed with a manual handle.

Motor operators run the motor from the 120V feed as the primary power source and uses the 12V battery as a backup. Because the motor operator uses AC as its primary power source, the motor operator will run if AC is present even if the battery is weak. AC and battery power are supplied to the motor concurrently. This means the motor operator will complete an operation without hesitation, even if AC is lost during the operation (such as having the distribution transformer on the load side of the switch).

The motor operator incorporates a stall timer that automatically terminates motor operation after a predefined time interval. If the motor operator stalls due to switch icing or a mechanical obstruction, the timer ends the operation before prolonged stall current can cause the DC fuse to open. This feature helps prevent the unit from becoming inoperable and reduces the need for field service associated with fuse replacement.

Enclosure and Wiring

Decoration

The motor operator enclosure offers sufficient room to house most RTUs and radios with all components accessible through the front door. The unit mounts easily to wood, steel, or concrete poles and can be installed at any height on the pole. The enclosure is powder coated white to provide a surface that reflects the heating rays of the sun, thereby reducing heat buildup within the enclosure increasing the lifetime of the battery.

Cleaveland/Price can factory install radios, RTU units, sensors, relays, and any other specialty device. When installed at the C/P factory, our production team will verify the functionality of each device, ensuring that the motor operator requires minimal field installation time.

By the Numbers (Ratings)

Decoration
Battery Charger VoltageOutput Torque (lbs)Operating Time (90°)Pipe Size (IPS)FeaturesSchematic DiagramWiring DiagramOutline Number
120VAC800 – 1400*0.4 seconds1” or 1.25”External RTU/radioC128B999C128B901CB29AA12
120VAC800 – 1400*0.4 seconds1” or 1.25”Internal RTU/radioC128B999N/ACB29AA04

Motor Operators and Controllers

Superior Reliability Through Design

Decoration

In everyday switching operations or emergency situations, a motor operator must operate when needed. Cleaveland/Price Inc. has been manufacturing motor operators since the 1990s and has developed field proven and reliable devices that give you the confidence that the motor will operate the switch when called upon. With thousands of installations throughout North America, Cleaveland/Price motor operators and controllers have demonstrated their dependability in a wide variety of environments and applications.