Center Break Switch
CB-A
The Cleaveland/Price CB-A is a three-pole, group-operated, aluminum center break switch for installation in substation or transmission line locations. The switch can be mounted in the horizontal upright, vertical, or horizontal underhung positions. The CB-A is suitable for use in a variety of applications including line disconnecting and sectionalizing, circuit breaker bypass and isolation, and transformer isolation. Arc horns or quick break whips can be supplied when small amounts of transformer magnetizing currents or line charging currents must be interrupted.
Accessories and options needed to adapt the switch to a customer’s particular requirements are available. The CB-A may be operated manually by use of a swing handle or wormgear mechanism, or electrically operated by use of a type TP-C2 or BT-T motor operator.
The CB-A meets applicable NEMA and IEEE Standards and the rating requirements of applicable IEC Standards.
Quality Construction
The CB-A continues the Cleaveland/Price tradition of designing simple, dependable switches without the use of castings. Knowledge gained from working with customers to identify and solve general switch problems has played a major part in refining the CB-A. Significant design features include:
- Total non-cast aluminum, copper, and steel parts resulting in superior dependability
- Live parts constructed from extruded aluminum and hard-drawn, high-conductivity copper, producing stronger, more conductive components than parts made of cast materials
- Silver-to-silver, high-pressure line contacts for effective transfer current
- Magnetically attracting parallel path hinge and jaw contacts for outstanding performance under short circuit
- Wiping action at both the jaw contacts and hinge contacts that keep the contacts clean for years of reliable service. Jaw contacts have a long contact wipe surface to accommodate insulator movement.
- Tin-plated copper terminal pads that can accept terminal connectors on three surfaces
- Aluminum to tin-plated copper bolted connections. All bolted contact surfaces are prepared and treated with an oxide inhibitor. Moving contacts are silver-to-silver with a hard-drawn, high-conductivity copper base material.
- Special hinge design supports high cantilever terminal loads while maintaining low pivot force
By the Numbers (Ratings)
| CB-A | Voltage Ratings | Amperage Ratings | |||||
|---|---|---|---|---|---|---|---|
| Catalog Number | Nominal Voltage (kV) | Maximum Voltage (kV) | BIL (kV) | Insulator TR No. | Continuous Current (A) | Peak Withstand Current (kA) | Short-Time Withstand Current (kA @ 3 sec.) |
| C0FB | 69 | 72.5 | 350 | 216 | 1200 | 99 | 38 |
| C0FC | 69 | 72.5 | 350 | 216 | 1600 | 114 | 44 |
| C0FD | 69 | 72.5 | 350 | 216 | 2000 | 164 | 63 |
| C0FF | 69 | 72.5 | 350 | 216 | 3000 | 195 | 75 |
| C0GB | 115 | 123 | 550 | 286 | 1200 | 99 | 38 |
| C0GC | 115 | 123 | 550 | 286 | 1600 | 114 | 44 |
| C0GD | 115 | 123 | 550 | 286 | 2000 | 164 | 63 |
| C0GF | 115 | 123 | 550 | 286 | 3000 | 195 | 75 |
| C0HB | 138 | 145 | 650 | 288 | 1200 | 99 | 38 |
| C0HC | 138 | 145 | 650 | 288 | 1600 | 114 | 44 |
| C0HD | 138 | 145 | 650 | 288 | 2000 | 164 | 63 |
| C0HF | 138 | 145 | 650 | 288 | 3000 | 195 | 75 |
| C0JB | 161 | 170 | 750 | 291 | 1200 | 99 | 38 |
| C0JC | 161 | 170 | 750 | 291 | 1600 | 114 | 44 |
| C0JD | 161 | 170 | 750 | 291 | 2000 | 164 | 63 |
| C0JF | 161 | 170 | 750 | 291 | 3000 | 195 | 75 |
| C0KB | 230 | 245 | 900 | 304 | 1200 | 99 | 38 |
| C0KC | 230 | 245 | 900 | 304 | 1600 | 114 | 44 |
| C0KD | 230 | 245 | 900 | 304 | 2000 | 164 | 63 |
| C0KF | 230 | 245 | 900 | 304 | 3000 | 195 | 75 |
| C0LB | 230 | 245 | 1050 | 312 | 1200 | 99 | 38 |
| C0LC | 230 | 245 | 1050 | 312 | 1600 | 114 | 44 |
| C0LD | 230 | 245 | 1050 | 312 | 2000 | 164 | 63 |
| C0LF | 230 | 245 | 1050 | 312 | 3000 | 195 | 75 |
| C0ND | 345 | 362 | 1300 | 324 | 2000 | 164 | 63 |
| C0NF | 345 | 362 | 1300 | 324 | 3000 | 195 | 75 |